EL
ErrorLib
Brands
||
  1. Home
  2. Schneider Electric
  3. XW Pro NA Operation Guide
  4. F31
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F31

AI L1 Over Voltage

Schneider Electric · XW Pro NA Operation Guide

What does F31 mean?

This fault indicates an L1 over-voltage condition (130 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to excessive voltage.

Common Causes

  • Grid L1-Neutral voltage exceeding 130 V for a sustained period, indicating persistent grid voltage instability or a utility over-voltage condition.
  • Gradual voltage creep on phase L1 due to an imbalanced grid or nearby generator operations, exceeding the slow trip threshold.
  • Inverter's L1 voltage sensing circuit drifting out of calibration or experiencing intermittent measurement errors over time.
  • Anti-islanding parameter P_AI_L1_Volt_Max_Slow set too close to nominal, causing frequent trips during minor voltage fluctuations.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Using a true RMS multimeter, continuously monitor the L1-Neutral voltage at the inverter's AC input terminal L1 over several hours to detect persistent high voltage.

  2. 2

    Compare the sustained L1-Neutral voltage readings against the specified 130 V trip threshold and the inverter's P_AI_L1_Volt_Slow parameter.

  3. 3

    Verify that the neutral conductor connection to the inverter (Terminal N) and the L1 phase terminal (Terminal L1) are secure and free from corrosion.

  4. 4

    Contact the utility provider to report sustained high voltage conditions on phase L1 at your site and request a grid voltage stability check.

  5. 5

    If external voltage is stable, verify the inverter's internal L1 voltage measurement offset parameter (e.g., P_AI_L1_Volt_Offset) for potential misconfiguration.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

F1AC Output Under VoltageF17Relay(s) WeldedF18Relay(s) Welded
Source: Schneider Electric XW Pro NA Operation Guide
View Official PDFSearch more codes in this manual