Schneider Electric · XW Pro NA Operation Guide
This fault indicates an L1-L2 over-voltage condition (260 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to excessive voltage.
Click steps to track your progress.
Using a true RMS multimeter, continuously monitor the L1-L2 phase-to-phase voltage at the inverter's input terminals over several hours to observe any sustained readings above 260 V.
Compare the measured L1-L2 voltage values against the inverter's configured anti-islanding slow trip threshold (e.g., P_AI_L1L2_Volt_Slow).
Verify the integrity of the main AC input cabling from the grid connection point to the inverter (e.g., for conductor size, termination quality).
Request a power quality survey from the utility provider or an electrical contractor to identify persistent over-voltage conditions on the L1-L2 phases.
If grid conditions are confirmed stable, consider adjusting the L1-L2 slow over-voltage parameter (e.g., P_AI_L1L2_Volt_Max_Slow) upwards slightly, if allowed by grid codes.