Schneider Electric · XW Pro NA Operation Guide
This fault indicates an L1 under-voltage condition (108 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to insufficient voltage.
Click steps to track your progress.
Using a true RMS multimeter, continuously monitor the L1-Neutral voltage at the inverter's AC input terminal L1 over several hours to detect persistent low voltage.
Compare the sustained L1-Neutral voltage readings against the specified 108 V trip threshold and the inverter's P_AI_L1_Volt_Min_Slow parameter.
Verify the tightness and condition of the L1 phase and neutral conductor connections at the inverter's input terminals (e.g., Terminal L1, Terminal N).
Investigate the local grid connection for other large loads drawing power from phase L1 that might cause voltage sags, especially during startup.
If external voltage is stable, verify the inverter's internal L1 voltage measurement offset parameter (e.g., P_AI_L1_Volt_Offset) for potential misconfiguration.