EL
ErrorLib
Brands
||
  1. Home
  2. Schneider Electric
  3. XW Pro NA Operation Guide
  4. F36
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F36

AI L1L2 Under Voltage

Schneider Electric · XW Pro NA Operation Guide

What does F36 mean?

This fault indicates an L1-L2 under-voltage condition (108 V equivalent based on F34 reference) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to insufficient voltage.

Common Causes

  • Grid L1-L2 phase-to-phase voltage dropping below the equivalent of 108 V phase-neutral (e.g., approx 216V line-line for 208V system) for a sustained period.
  • Widespread utility grid under-voltage condition, brownout, or high impedance feeder cable causing voltage drop across L1 and L2 phases.
  • Inverter's internal L1-L2 voltage measurement hardware showing inaccuracies or component fatigue, leading to false low voltage readings.
  • Anti-islanding parameter P_AI_L1L2_Volt_Min_Slow set too high, causing nuisance trips on minor grid voltage fluctuations.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Using a true RMS multimeter, continuously monitor the L1-L2 phase-to-phase voltage at the inverter's input terminals over several hours to observe any sustained readings below the expected 108V equivalent.

  2. 2

    Compare the measured L1-L2 voltage values against the inverter's configured anti-islanding slow trip threshold (e.g., P_AI_L1L2_Volt_Slow).

  3. 3

    Inspect the integrity of the AC input cabling from the grid connection point to the inverter (e.g., conductor termination, correct cable sizing).

  4. 4

    Contact the utility provider to report sustained low voltage conditions on the grid and inquire about local power quality or ongoing maintenance.

  5. 5

    If grid conditions are confirmed stable, consider adjusting the L1-L2 slow under-voltage parameter (e.g., P_AI_L1L2_Volt_Min_Slow) downwards slightly, if allowed by grid codes.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

F1AC Output Under VoltageF17Relay(s) WeldedF18Relay(s) Welded
Source: Schneider Electric XW Pro NA Operation Guide
View Official PDFSearch more codes in this manual