Schneider Electric · XW Pro NA Operation Guide
This is an Escalating Automatic Fault that occurs when the auxiliary power supply experiences an under-voltage shutdown. If this condition triggers 3 times within 30 seconds, it becomes a manual fault, indicating persistent power issues for control circuitry.
Click steps to track your progress.
Measure the auxiliary power supply output voltage (e.g., 24VDC, 12VDC) at its terminals under varying loads using a multimeter.
Disconnect all loads from the auxiliary power supply and measure its open-circuit voltage to determine if the APS itself is faulty.
Measure the input voltage to the auxiliary power supply to ensure it meets the specified range (e.g., 240VAC +/- 10% or 48VDC nominal).
Systematically disconnect external devices powered by the APS one by one, while monitoring APS output voltage, to identify an overloaded branch.
Inspect all wiring connected to the auxiliary power supply output for physical damage, loose connections, or signs of overheating that indicate high resistance.