F42

APS Over Voltage

Schneider Electric · XW Pro NA Operation Guide

What does F42 mean?

This is an Escalating Automatic Fault that occurs when the auxiliary power supply experiences an over-voltage shutdown. If this condition triggers 3 times within 30 seconds, it becomes a manual fault, indicating persistent excessive voltage for control circuitry.

Common Causes

  • Faulty auxiliary power supply (APS) module itself, regulating its output voltage too high.
  • Absence of load or extremely light load on the APS output, causing voltage to spike if the regulation circuit is unstable.
  • Improper input voltage to the APS, exceeding its operational limits and causing internal components to fail.
  • Defective voltage sensing or feedback circuit within the APS, preventing proper voltage regulation.
  • Transient voltage spikes on the input power lines feeding the auxiliary power supply.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the auxiliary power supply output voltage (e.g., 24VDC, 12VDC) at its terminals with all loads connected using a multimeter.

  2. 2

    Disconnect all loads from the auxiliary power supply and measure its open-circuit voltage to verify if the APS is over-voltage even without load.

  3. 3

    Measure the input voltage to the auxiliary power supply to ensure it remains within its specified operational range and does not exceed upper limits.

  4. 4

    Check for any external devices (e.g., regenerative braking units) that might be backfeeding voltage onto the APS output lines.

  5. 5

    Perform a factory reset of inverter parameters (e.g., Parameter P0-01 to "Reset") and reconfigure essential settings, in case software misconfiguration affects APS.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026