This Automatic Fault indicates a DC under-voltage shutdown that occurs if the DC voltage stays below the Low Battery Cut Out (LBCO) for a specified delay. The inverter restarts when the voltage reaches LBCO + LBCO Hysteresis, suggesting similar troubleshooting steps as F47.
Click steps to track your progress.
1. Measure actual DC bus voltage at the inverter's DC input terminals (e.g., DC+ and DC-) using a calibrated multimeter.
2. Verify the battery bank's state of charge and measure individual battery cell voltages under load to identify weak cells (e.g., cells below 2.0V).
3. Inspect DC bus cabling for loose connections at terminals, corrosion, or signs of overheating. Torque terminals to manufacturer specifications (e.g., 20 Nm).
4. Review inverter parameter (e.g., P3-10 or 'Low Battery Cut Out') and adjust if necessary, ensuring it aligns with battery manufacturer's discharge recommendations.
5. Check for excessive load on the DC bus that might be drawing current beyond the battery or supply capability.