Schneider Electric · XW Pro NA Operation Guide
This Automatic Fault occurs when the internal temperature of FET1 exceeds 105 °C, triggering a shutdown to protect the inverter's power components. The fault clears automatically when the temperature drops to 75 °C.
Click steps to track your progress.
1. Power down the inverter, disconnect AC and DC sources, and allow components to cool (e.g., 30 minutes).
2. Inspect all cooling fan(s) for proper operation, verify fan rotation, and clean any dust buildup from fan blades and heatsink fins using compressed air.
3. Measure the ambient temperature around the inverter and ensure it is within the manufacturer's specified operating range (e.g., -20°C to +45°C).
4. Verify that the load connected to the inverter's AC output does not exceed its continuous power rating (e.g., check output current via display or clamp meter).
5. Check for loose mounting screws or improper seating of FET1 to its heatsink, ensuring adequate thermal transfer.