This Escalating Automatic Fault occurs due to an excessive load specifically on AC output line 1. If triggered 3 times in 5 minutes, it becomes a manual fault, indicating that line 1's capacity is being consistently exceeded.
Click steps to track your progress.
1. Measure the current on AC output Line 1 at the inverter terminal using a clamp meter and compare it to currents on other lines (L2, L3 if applicable).
2. Redistribute loads across different AC output lines to balance the current draw on Line 1.
3. Isolate individual loads connected to Line 1 by disconnecting them sequentially to identify the specific faulty or oversized load.
4. Inspect wiring and connected devices on AC output Line 1 for insulation breakdown, loose connections, or short circuits.
5. Review inverter's overload trip settings for individual phases (e.g., P2-12 'L1 Overload Current Limit') and adjust based on actual load and inverter specifications.