Schneider Electric · XW Pro NA Operation Guide
This Automatic Fault indicates incorrect multi-unit configuration settings, such as more than one primary unit or non-unique device numbers in a multi-inverter setup. This prevents proper system synchronization and operation.
Click steps to track your progress.
1. Access each inverter's configuration menu and verify that only one unit is set as the 'Master' or 'Primary' (e.g., P0-02) and all others are 'Slave' or 'Secondary'.
2. Ensure all units in the multi-inverter system have unique device IDs or communication addresses (e.g., P0-03) on the network.
3. Verify that all inverters in the system are running the same firmware version. If not, update firmware on all units to match.
4. Inspect the communication cabling (e.g., CAN bus, RS485) between units, checking for proper termination resistors (e.g., 120 Ohm) and secure connections at each terminal.
5. Perform a system-wide reset of configuration parameters on all units, then reconfigure them sequentially, starting with the designated master unit.