This Manual Fault occurs when the External AC Contactor or a latching relay within the Battery Control System (BCS) is not in its expected commanded state. This signifies a failure in the external AC power path control, impacting power flow.
Click steps to track your progress.
1. Visually inspect the external AC contactor for physical damage, discoloration from overheating, or signs of welded main contacts.
2. Using a multimeter, measure the voltage across the contactor's coil terminals (e.g., A1-A2) when commanded to change state by the BCS.
3. Verify continuity of the contactor's auxiliary feedback contacts (e.g., 13NO-14NO) in both open and closed states, comparing to the BCS expected state.
4. Inspect all control wiring from the BCS to the external AC contactor for proper termination, continuity, and insulation integrity.
5. Power cycle the Battery Control System (BCS) and observe if the contactor attempts to actuate and its state changes.