Schneider Electric · XW Pro NA Operation Guide
This Automatic Fault indicates that a primary or secondary AC1 or AC2 breaker has tripped in a multi-unit installation, likely due to an overload condition. The inverter will attempt to auto-clear the fault once the breaker is closed.
Click steps to track your progress.
1. Identify and manually reset the tripped primary or secondary AC breaker (e.g., AC1 output breaker) at the distribution panel.
2. Measure the load current on the AC output circuit (e.g., using a clamp meter on L1, L2, L3) and compare it to the breaker's ampere rating.
3. Perform an insulation resistance test (e.g., using a Megger MIT420/2) on the AC output wiring downstream of the breaker to detect ground faults or shorts.
4. Inspect the tripped AC breaker for any physical damage, discoloration, or signs of arcing, which could indicate internal failure.
5. Temporarily disconnect non-critical loads from the AC output to reduce the total load and re-test the circuit.