SEW Eurodrive · MCBSM
A ground fault has been detected in the motor, its supply lead, or within the MOVITRAC® B inverter itself, causing an immediate switch-off with inhibit. This is a critical safety and equipment protection issue. Unresolved ground faults can lead to severe damage or safety hazards.
Click steps to track your progress.
1. Disconnect the motor cable from the inverter output (U, V, W) and measure insulation resistance from each phase to ground (expect >10 Mohms).
2. Visually inspect the motor terminal box and cable glands for moisture, corrosion, or insulation damage.
3. Verify that the motor frame is properly grounded (e.g., resistance to protective earth <1 Ohm) according to local electrical codes.
4. If the fault clears with the motor disconnected, focus troubleshooting on the motor and cabling; if the fault persists, suspect an inverter internal issue.
5. Use a megohmmeter (e.g., 1000V DC) to test insulation of motor windings and the motor cable to ground and between phases.