This fault indicates that the MOVIFIT unit was unable to automatically detect or recognize the sequence of the incoming three-phase power supply during its initialization phase. This prevents the unit from starting correctly and is typically due to incorrect wiring of the grid connection (L1, L2, L3). An unrecognized phase sequence can lead to motors rotating in the wrong direction, damage to mechanical components, or unit malfunction, requiring immediate correction before operation.
Click steps to track your progress.
Measure the incoming line voltages (L1-L2, L2-L3, L3-L1) at the MOVIFIT input terminals immediately after power-up using a true-RMS multimeter.
Verify the stability of the incoming power supply by monitoring voltages over a short period to detect sags or swells using a power quality meter.
Inspect all input power connections at the MOVIFIT unit, upstream contactors, and circuit breakers for tightness and corrosion.
Check all line fuses (L1, L2, L3) upstream of the MOVIFIT unit for continuity using a multimeter.
Attempt a full power cycle of the MOVIFIT unit and its main power supply to re-initiate the grid detection sequence.