This fault indicates various forms of motor overload or overtemperature protection. It can be triggered by cyclical monitoring exceeding limits (due to frequent starts/stops or high load), by UL protection functions detecting time violations of current limits (e.g., 750% IN,unit), or by the internal motor temperature simulation reaching 110% utilization. These protections safeguard the motor and drive from damage due to excessive mechanical load, demanding duty cycles, or insufficient cooling. Unresolved overload conditions lead to reduced motor lifespan and potential drive unit failure.
Click steps to track your progress.
Monitor the motor's actual operating current and temperature profile during a typical work cycle using diagnostic tools (e.g., P304 for current, P306 for temperature).
Increase acceleration and deceleration ramp times (e.g., P320/P321 for drive 1, P330/P331 for drive 2) to reduce peak currents during start/stop.
Verify the motor thermal model parameters (P308, P309 for drive 1; P318, P319 for drive 2) against the motor's actual thermal specifications and duty cycle.
Check the mechanical load on the motor for any binding, obstructions, or excessive friction that would increase current draw.
Inspect the motor's cooling fan for proper operation and ensure all cooling air passages on the motor are clear of debris.