This fault indicates that the internal speed monitoring function has detected a condition where the actual speed deviates significantly from the commanded speed, typically due to excessive load. This fault occurs only when DIP switch S2/4 is set to 'ON', and can cause the motor to stall or operate outside its designed parameters.
Click steps to track your progress.
Reduce the mechanical load on the drive.
Verify DIP switch S2/4 is correctly set if speed monitoring is intended to be active.
Reset the fault by switching off and then switching on the DC 24V supply voltage.
Reset the error via the error reset function.