43

Cyclical Communication Timeout

SEW Eurodrive · MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc

What does 43 mean?

This fault indicates a timeout during cyclical communication via the RS-485 interface, causing the drive to decelerate and stop along the set ramp. A communication timeout means the MOVIMOT unit is not receiving expected data from the RS-485 master within the configured interval (e.g., 1 second).

Common Causes

  • Interruption or faulty communication link between the RS-485 master and the MOVIMOT unit.
  • Too many slave units connected to the RS-485 master for the configured timeout interval (maximum 8 MOVIMOT inverters for a 1s timeout).
  • EMC influence on data lines due to inadequate shielding.
  • Incorrect message cycle duration or selection of cyclical message type with prolonged protocol time between messages (longer than 1s).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check and establish the communication link (RS+, RS-, earth) between the RS-485 master and the MOVIMOT unit.

  2. 2

    Check shielding of data lines and improve if necessary to reduce EMC influence.

  3. 3

    Verify the number of slaves connected to the RS-485 master; ensure it does not exceed 8 MOVIMOT inverters if the timeout interval is 1 second.

  4. 4

    Reduce the message cycle time or select 'acyclic' message type if applicable.

Browse all codes in this manual (23)