This error is generated if the drive operates at its adjustable current limit for longer than 500 ms, occurring when additional function 2 (adjustable current limitation) is active and the operating frequency is above 15 Hz. Prolonged operation at current limit can indicate an overloaded condition.
Click steps to track your progress.
Check the mechanical load on the drive and reduce it if necessary.
Review the setting of DIP switch f2 for the adjustable current limit (Imax [%] of IN) and increase it if appropriate for the application.
Verify the operating frequency is above 15 Hz, as this monitoring function is active only then.
Reset the fault by switching off and then switching on the DC 24V supply voltage.
Reset the error via the error reset function.