SEW Eurodrive · MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc
This fault indicates a thermal overload of the brake coil or a defect within the brake itself, including incorrect connection. Overtemperature can lead to reduced braking force, premature wear, or complete failure of the brake mechanism.
Click steps to track your progress.
Increase the set ramp time to reduce brake stress.
Perform a brake inspection (refer to 'DR/DV/DT/DTE/DVE Series AC Motors' operating instructions').
Check the brake coil connection for correct wiring and integrity.
Check the combination of the drive (brake coil) and MOVIMOT inverter if the fault is signaled shortly after the first enable.
For 'MOVIMOT and motor with one lower power rating' combinations, check the setting of DIP switch S1/6.
Reset the fault by switching off and then switching on the DC 24V supply voltage.