SEW Eurodrive · MOVITRAC 07B System
An immediate switch-off with inhibit occurs when the current controller operates at its set limit, indicating issues such as mechanical overload, line phase failure, motor phase failure, or exceeding the maximum speed in VFC operating modes. Parameter P501 is relevant for deceleration time.
Click steps to track your progress.
Reduce the mechanical load on the motor
Check current limitation settings
Extend deceleration ramps and increase the set deceleration time (P501)
Check line phases at the inverter input
Check the motor cable and the motor phases for continuity
Reduce the maximum speed setting if operating in VFC mode