F36

Option missing

SEW Eurodrive · MOVITRAC 07B System

What does F36 mean?

An option card is either incorrect, missing, or has incompatible settings for its setpoint source, control signal, or operating mode. This fault indicates a configuration mismatch or hardware absence, leading to an immediate switch-off with inhibit.

Common Causes

  • Installation of an unsupported or incorrect type of option card
  • Setpoint source, control signal source, or operating mode parameters are incompatible with the installed option card
  • Required option card (e.g., FBG11B, FIO12B, FIO21B) is not present
  • Front module FIO21B is not supplied with power

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Install the correct type of option card for the application.

  2. 2

    Verify parameters for setpoint source, control signal source, and operating mode are compatible with the installed option card.

  3. 3

    Check parameters P120 and P121 for general option card configuration.

  4. 4

    If FBG11B is used, check parameter P121. If FIO12B is used, check P120 and P642.

  5. 5

    If FIO21B is installed, set parameter P808 to "On" or supply the basic unit with external 24V.