F43

RS485 timeout

SEW Eurodrive · MOVITRAC 07B System

What does F43 mean?

Communication over the RS485 interface between the inverter and a PC, or to the FSE24B module, has been interrupted. This fault does not lock the drive and clears automatically once communication is reestablished, indicating a transient or connection issue.

Common Causes

  • Physical connection interruption between the inverter and a PC via RS485
  • Interruption in communication link to the FSE24B interface module
  • Loss of voltage supply to the FSE24B communication module

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the physical RS485 connection cable between the inverter and the PC.

  2. 2

    Check the voltage supply to the FSE24B communication interface module.

  3. 3

    Inspect parameter P808 settings related to auxiliary voltage output, which might affect FSE24B power.