FF0204h
Software Limit Switch CCW Exceeded
SEW Eurodrive · MOVI-PLC SyncCrane Application
What does FF0204h mean?
This fault indicates that the specified position or the actual position of an axis has moved beyond the defined counter-clockwise (CCW) software limit switch. This condition prevents further movement in the CCW direction and halts the axis system to prevent overtravel.
Common Causes
- Axis position exceeded the defined counter-clockwise software limit switch.
- Encoder feedback indicates movement beyond the minimum allowed CCW position.
- Incorrectly set CCW software limit parameter.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Review and adjust the counter-clockwise software limit parameter (e.g., P5-41) to a lower value.
- 2
Manually move the axis to a safe position within the limits.
- 3
Check the actual encoder position reading (e.g., P5-03) to confirm it is within the new limits.
- 4
Ensure the homing procedure correctly sets the initial reference position.
Verified technical data. Last updated: March 2026
Related Faults
Source: SEW Eurodrive MOVI-PLC SyncCrane Application