The system is attempting to use a configuration that the power unit does not support. This can be caused by requesting autonomous operation on an unsupported unit, incompatible DRIVE-CLiQ timing, an older PM260 PS-ASIC version, failed initialization due to premature Control Unit withdrawal, or an unsupported combination of power unit and Control Unit/Adapter. The fault value in r0949 provides specific details on the cause.
Click steps to track your progress.
Verify the exact model number (MLFB) of the power unit and its technical specifications for supported operating modes.
Check parameter P0003 (User access level) and P0010 (Control unit configuration) to ensure no unsupported autonomous mode is selected.
Compare DRIVE-CLiQ configuration parameters (P0922, P0923, P0927) in the drive with the project configuration in STARTER/TIA Portal.
Perform a DRIVE-CLiQ topology scan (automatic configuration) to re-establish communication and identify modules.
Ensure the firmware version of the control unit is compatible with the power unit's firmware version, updating if necessary.