Siemens · DAsl Diagnostics and Alarms
The reactor module has detected an overtemperature condition or a failure in its cooling fan. This alarm serves as a warning for a potential thermal issue. If this alarm persists for longer than 30 seconds, it will escalate to fault F37313 (likely 237313), indicating a more critical and sustained thermal problem that requires immediate attention.
Click steps to track your progress.
Inspect the HF reactor module's fan during operation to confirm it is rotating freely and at full speed.
Clean the air filters and cooling vents of the control cabinet and the reactor module itself.
Monitor the load on the drive system (r0067) to identify transient overloads; reduce load if necessary.
Measure the internal cabinet temperature and compare it to the module's specified maximum operating temperature.
Check the reactor's internal temperature sensor feedback (r0037, if available) against ambient readings and expected values.