Siemens · DAsl Diagnostics and Alarms
This fault is triggered when alarm A37312 (237312), indicating an overtemperature or fan failure in the reactor module, has been active for more than 30 seconds. This signifies a persistent and critical cooling problem that could lead to severe damage or shutdown of the reactor module if not addressed. Reaction is OFF2, requiring an immediate power on acknowledge.
Click steps to track your progress.
Immediately power down the system and replace the cooling fan of the HF reactor module if it is not operating.
Perform a thorough cleaning of all air passages, heat sinks, and fans within the control cabinet and on the reactor module.
Reduce the operational load on the system to ensure the average current (r0067) remains below the reactor's rated continuous current.
Install additional cabinet cooling (e.g., air conditioning unit, larger fans) if the measured ambient temperature consistently exceeds specifications.
Disconnect the reactor and perform an insulation resistance test (megohmmeter) on its windings to ground and phase-to-phase.