Siemens · DAsl Diagnostics and Alarms
An alarm has been detected at the drive object connected to the DRIVE-CLiQ socket X100. The alarm value (r2124) indicates the first alarm that occurred for this specific drive object. This signals a potential issue with the communication or connected component on this DRIVE-CLiQ interface that requires attention to prevent escalation to a fault or performance degradation.
Click steps to track your progress.
Read the alarm value in register r2124 associated with A40100; this will indicate the specific warning or alarm from the connected DRIVE-CLiQ device.
Power off the drive, then inspect and firmly re-seat the DRIVE-CLiQ cable at both the Control Unit's X100 socket and the connected drive object's (e.g., Motor Module) DRIVE-CLiQ port.
Check the DRIVE-CLiQ cable for physical integrity, paying close attention to bends, strains, or potential damage points.
Verify the proper shielding and grounding of the DRIVE-CLiQ cable to minimize external electromagnetic interference.
Cycle power to the drive system; sometimes transient communication issues or warnings can resolve with a restart.