Siemens · DCM
The motor is currently being braked using DC current, which is a normal operational state. This alarm appears when a message with a 'DCBRK' response is active, injecting the braking current (p1232) for a duration (p1233) or until the standstill threshold (p1226) is undershot. It can also be activated manually via binector input p1230. This is an informational alarm and does not indicate a fault.
Click steps to track your progress.
1. Verify the active command source for DC braking (e.g., check status of digital input BICO-connected to P1230).
2. Review parameter P1230 (DC braking switch on) to confirm whether DC braking is enabled by an external signal or automatically.
3. Check parameter P1231 (DC braking switch on for braking ramp) to see if DC braking is configured for automatic activation after deceleration.
4. Observe the motor current (r0027) during the 'DC braking active' alarm to confirm DC current injection.
5. If this alarm is unexpected, investigate the machine's control logic (PLC program) to identify the condition triggering the DC braking command.