Siemens · DCM
This alarm indicates that the internal temperature within the power unit has reached its alarm threshold. If the temperature continues to rise, it could lead to fault F30036. Common causes include high ambient temperature or insufficient cooling due to fan failure. Unresolved, it risks power unit damage or shutdown.
Click steps to track your progress.
Measure the temperature inside the drive cabinet at various points (e.g., top, middle, bottom) using an infrared thermometer.
Verify the operation of all internal cooling fans by visual inspection or current measurement (e.g., across fan power terminals).
Inspect and clean all air intake and exhaust vents on the drive and cabinet, removing any dust or obstructions with compressed air (low pressure).
Check drive parameters P1-03 (Max output current) and P1-04 (Motor rated current) for correct values matching the motor nameplate.
Monitor the actual motor current (e.g., Parameter P2-01) under load and compare it to the drive's continuous current rating.