Siemens · DCM
This alarm indicates that the cooling fan in the power unit has reached or exceeded its specified maximum operating hours (typically 500 hours), as configured in p0252. While the fan may still be operational, this serves as a preventative maintenance alert. Continuing to operate with an aged fan increases the risk of fan failure and subsequent overtemperature faults, potentially damaging the power unit.
Click steps to track your progress.
Read the current fan operating hours from parameter r0251; compare it to the fan's rated lifetime and P0252.
Inspect the cooling fan for any unusual noises, vibrations, or reduced airflow, even if it appears to be rotating.
Plan for proactive replacement of the cooling fan as it is nearing its end of life according to the set threshold.
After replacing the fan, reset the operating hours counter by setting parameter P0251 = 0 and confirming the change.
Review parameter P0252; adjust it if necessary to match the expected lifespan of the installed fan for future alerts.