The internal cooling fan within the power unit has failed. This is a critical alarm as the fan is essential for dissipating heat. Continued operation without a functional fan will rapidly lead to overtemperature faults and potentially irreversible damage to the power unit's electronics.
Click steps to track your progress.
Power off the drive and lock out. Visually inspect the internal cooling fan for any physical damage, obstructions, or complete stoppage.
Gently attempt to rotate the fan blades manually (with power off) to check for binding, resistance, or seized bearings.
Check the fan's electrical connector on the power unit's circuit board for secure seating and continuity.
Listen for any fan rotation noise immediately after power-up; a complete lack of sound confirms fan failure.
Replace the faulty internal cooling fan with an original manufacturer's replacement part, ensuring correct model and proper installation.
After replacement, clear any pending fan faults (e.g., using P0254 = 1) and monitor internal temperatures (r0035, r0036) during operation.