Siemens · DCM
The drive has lost its "sign-of-life" signal from an active PC master control within the configured monitoring time, indicating a communication interruption. Consequently, master control has reverted to the BICO interconnection. This fault stops PC-based control, potentially leading to an uncontrolled state or production halt.
Click steps to track your progress.
Verify the physical communication cable integrity (e.g., Profinet RJ45, Profibus DB9 connector) between the master control and the drive.
Check the master controller program logic to ensure the cyclic telegram (e.g., PZD, control word) is actively sending data to the drive.
Increase the monitoring time parameter (e.g., P2040) in the drive configuration in increments (e.g., 100ms, 200ms) to accommodate network latency.
Diagnose the communication interface module status LEDs (e.g., Link/Act, SF on CBE20) for any error indications.
Ping the drive's IP address (for Profinet) or check network status (for Profibus) from the master controller to verify basic network connectivity.
Verify the communication telegram configuration (e.g., P918 for send PZD, P922 for receive PZD) matches both master and drive.