Siemens · DCM
This fault indicates that the measured DC link voltage is outside the expected tolerance range after the pre-charging process, based on the parameterized supply voltage (p0210). This could be due to incorrect parameter settings or an actual issue with the incoming line supply voltage. Operating with incorrect voltage parameters or an unstable supply can lead to drive malfunction or damage.
Click steps to track your progress.
Measure the actual AC line-to-line voltage at the drive's input terminals (L1-L2, L2-L3, L3-L1) with a true RMS voltmeter.
Compare the measured voltage to the value set in parameter P0210; adjust P0210 to accurately reflect the supply voltage.
Verify continuity and presence of all three input phases (L1, L2, L3) using a multimeter; check upstream fuses and circuit breakers.
Observe the DC link voltage (r0026) after the pre-charging sequence; it should be stable and approximately 1.35 times P0210 (for 3-phase AC).
Inspect all power connections from the main supply to the drive's input terminals for tightness and corrosion.
Cycle power to the drive and observe the pre-charging sequence; check pre-charge resistors for signs of overheating if fault recurs rapidly.