Siemens · DCM
An error was detected during the evaluation of the motor temperature sensor (configured in p0601). Possible causes include a wire breakage (KTY: R > 2120 Ohm), the sensor not being connected, or a measured resistance that is too low due to a short circuit (PTC: R < 20 Ohm, KTY: R < 50 Ohm). If alarm A07015 was present, this fault was output after the timer p0607 expired, indicating a prolonged issue.
Click steps to track your progress.
1. Measure resistance across motor temperature sensor terminals (e.g., X9:1 and X9:2) at the drive using a multimeter. Verify resistance is within the expected range (e.g., 200-2120 Ohm for KTY84 at typical operating temperatures).
2. Check continuity of the motor temperature sensor cable from the drive's X9 terminals to the motor's sensor leads using a multimeter.
3. Verify parameter P0601 (Motor temperature sensor type) setting matches the actual sensor installed in the motor (e.g., KTY84, PT100, PT1000).
4. Inspect internal motor temperature sensor wiring for damage or disconnections inside the motor terminal box.
5. If resistance measurement is out of range, replace the motor temperature sensor (if accessible) or the motor itself.