Siemens · DCM
For PM250 and PM260 blocksize power units, the regenerative rated power (r0206[2]) was continuously exceeded for more than 10 seconds. This indicates that the drive is generating excessive energy back into the DC bus or supply, which can lead to overvoltage and potential damage if the regeneration capability is insufficient.
Click steps to track your progress.
1. Increase deceleration time (P1121) to reduce the rate of energy regeneration during braking.
2. Verify the connected braking resistor's resistance value with an ohmmeter and compare it to P0219.
3. Check the braking resistor thermal fuse for continuity and ensure proper ventilation around the resistor bank.
4. Monitor r0206[2] (Regenerative power) during operation to quantify the peak and average regenerative power.
5. Consider increasing the braking resistor power rating or adding an additional braking resistor module if r0206[2] consistently exceeds capacity.