Siemens · DCM
A phase-to-phase short-circuit has been detected at the motor-side output terminals of the converter. This is a critical fault that can severely damage the power unit if not resolved. It can also be triggered if the line (input) and motor (output) cables are accidentally interchanged, creating a short circuit condition.
Click steps to track your progress.
1. Disconnect the motor cables from the drive's output terminals (U, V, W).
2. Measure resistance between motor phases (U-V, V-W, W-U) at the disconnected motor cable ends using a multimeter to detect a short-circuit (< 1 Ohm).
3. Perform an insulation resistance test (Megger test) between each motor phase and ground, and between phases, at the motor terminals.
4. Inspect the drive's output terminals for signs of arcing, carbon tracking, or conductive debris.
5. If the motor cable or motor itself is confirmed shorted, replace the damaged component. If they test clear, replace the drive's power module or the entire drive unit.