No rated data is stored in the power unit's EEPROM, which is essential for the drive to operate correctly. This can indicate a faulty EEPROM, an uninitialized power unit, or a replacement unit that has not been properly configured. Without this data, the drive cannot determine its nominal operating characteristics.
Click steps to track your progress.
1. Perform a full parameter reset (P0010 = 30, P0970 = 1) followed by re-entering all motor and application parameters.
2. If available, restore parameters from a previously saved backup file (e.g., via STARTER or TIA Portal software).
3. Ensure the Control Unit (e.g., CU240E) is correctly mounted and securely connected to the power module.
4. Attempt a firmware update of the drive, ensuring a stable power supply and proper procedure is followed.
5. If the fault persists after parameter restore and firmware update, replace the drive's power unit (e.g., PM240).