Siemens · DCM
The internal temperature of the drive converter, specifically in the control or power electronics, has exceeded its safe operating limit. This can be caused by inadequate cooling (fan failure), motor overload, or excessive ambient temperatures. Continued operation risks severe damage to the power unit.
Click steps to track your progress.
De-energize the drive and verify the free rotation and condition of all internal cooling fans (e.g., power module fan, control unit fan).
Inspect and thoroughly clean heat sinks of any dust, lint, or debris using a vacuum cleaner and non-conductive compressed air.
Check drive parameters P1-04 (Motor rated current) and P1-05 (Motor rated speed) against the motor nameplate for correctness.
Measure the cabinet internal temperature at the drive location using an infrared thermometer and compare to the drive's specified max operating temperature.
Monitor the drive's output current (e.g., Parameter P2-01) under typical load conditions and compare to the drive's continuous current rating.
Perform a visual inspection of the thermal interface materials if previous steps do not resolve the issue (requires disassembly).