Siemens · DCM
For 3P gating units, the end ID for the last switching status word in the setpoint telegram was not found. This signifies a communication or data integrity issue with the switching information, which is critical for the correct operation of the gating unit. This can lead to incorrect or no switching action of the power semiconductors.
Click steps to track your progress.
Perform a power cycle of the drive system (main power off/on) to reinitialize Drive-Cliq communication.
Inspect the Drive-Cliq cable connecting the control unit and power unit for damage, loose connectors, or incorrect length.
Verify the Drive-Cliq topology and component IDs are correctly configured in the engineering software (e.g., STARTER/TIA Portal).
Check the Drive-Cliq diagnostic messages (e.g., r0947, r0949 for Drive-Cliq faults) on the control unit for specific communication errors.
If possible, swap the Drive-Cliq cable with a known good one to rule out cable integrity issues.