Siemens · SINAMICS G120
This alarm indicates an issue with the PROFIBUS communication, specifically that an incorrect parameter or configuration telegram was received. This prevents the drive from being properly controlled or configured via the bus, leading to communication failure with the master.
Click steps to track your progress.
1. Verify the drive's PROFIBUS address (P2020) and baud rate (P2012) match the configuration in the PLC/controller's hardware configuration.
2. Ensure the correct GSD file for the specific drive model and firmware version is imported and used in the PLC/controller project.
3. Compare the PROFIBUS telegram configuration (e.g., P2051 - send PZD, P2053 - receive PZD) in the drive with the PLC's mapping for consistency.
4. Check the PROFIBUS cable integrity, termination resistors (e.g., at X101 terminals), and connector pins for damage or loose connections.
5. Perform a cold restart of both the drive and the PROFIBUS master (PLC) to re-initialize communication.
6. Use a PROFIBUS diagnostic tool to analyze the bus traffic and identify any corrupted telegrams or communication errors.