A00705

PROFIBUS: timeout actual value

Siemens · SINAMICS G120

What does A00705 mean?

The drive has experienced a PROFIBUS communication timeout, specifically indicating that no actual data is being received from the Control Unit Processor (CUP). This can lead to a loss of real-time operational data, affecting monitoring and control if not addressed promptly, potentially halting automated processes.

Common Causes

  • PROFIBUS master communication failure (e.g., PLC stopping, bus fault, or entering an error state) ceasing data transmission.
  • Loose or damaged PROFIBUS cable connection at the drive terminal (X100) or at the master device.
  • Missing or incorrectly placed PROFIBUS termination resistor (RS-485 termination) on the bus segment, causing signal reflections.
  • Incorrect PROFIBUS station address (P0918) set on the drive, preventing it from responding to the master's requests.
  • Intermittent electrical noise or strong electromagnetic interference (EMI) on the PROFIBUS network disrupting data packets.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the PROFIBUS master (e.g., PLC) is running, actively communicating, and configured correctly by checking its diagnostic LEDs or software status.

  2. 2

    2. Inspect PROFIBUS cable connections at the drive's X100 terminal and the master device for proper seating, secure fastening, and physical damage.

  3. 3

    3. Measure resistance across PROFIBUS Data A and Data B lines (X100 terminals 3 and 8) with power off to confirm proper bus termination (should be ~110-130 ohms with two terminations).

  4. 4

    4. Check PROFIBUS address parameter P0918 in the drive and ensure it precisely matches the address configured in the PROFIBUS master's hardware configuration.

  5. 5

    5. Observe the PROFIBUS communication LEDs on the drive (e.g., BF, SF) for activity or error indications, which can provide further diagnostic information.