Siemens · SINAMICS G120
The drive has experienced a PROFIBUS communication timeout, specifically indicating that no actual data is being received from the Control Unit Processor (CUP). This can lead to a loss of real-time operational data, affecting monitoring and control if not addressed promptly, potentially halting automated processes.
Click steps to track your progress.
1. Verify the PROFIBUS master (e.g., PLC) is running, actively communicating, and configured correctly by checking its diagnostic LEDs or software status.
2. Inspect PROFIBUS cable connections at the drive's X100 terminal and the master device for proper seating, secure fastening, and physical damage.
3. Measure resistance across PROFIBUS Data A and Data B lines (X100 terminals 3 and 8) with power off to confirm proper bus termination (should be ~110-130 ohms with two terminations).
4. Check PROFIBUS address parameter P0918 in the drive and ensure it precisely matches the address configured in the PROFIBUS master's hardware configuration.
5. Observe the PROFIBUS communication LEDs on the drive (e.g., BF, SF) for activity or error indications, which can provide further diagnostic information.