Siemens · SINAMICS G120
A fatal software error has occurred within the PROFIBUS communication module, potentially related to hardware checks, general communication issues, or problems with the V1SL stack. This critical error can lead to a complete loss of PROFIBUS connectivity and drive control, rendering the system inoperable via PROFIBUS.
Click steps to track your progress.
1. Power cycle the drive by disconnecting and reconnecting the main supply voltage, then observe if the fault clears upon restart.
2. Verify the PROFIBUS GSD file used in the master's hardware configuration is the correct and latest version for the drive's firmware revision.
3. Update the drive's firmware to the latest available version, especially if known bugs related to PROFIBUS communication are documented.
4. Test the drive with a known-good PROFIBUS communication board (CB) if available, to rule out a hardware fault on the existing board.
5. Temporarily disconnect the PROFIBUS cable from the X100 terminal and restart the drive to see if the fault persists, which helps isolate bus issues from internal hardware.