Siemens · SINAMICS G120
An inconsistency has been detected in the safety input signals, specifically related to the Safe Limited Speed (SLS) function. The drive will initiate a controlled deceleration (SS1) and eventually enter a Safe Torque Off (STO) state, issuing a fault due to the potential compromise of safety integrity.
Click steps to track your progress.
1. Verify the state of the redundant safety input signals (e.g., F-DI0 and F-DI1) directly at the drive's safety terminals (X150) using a multimeter (24VDC expected).
2. Check continuity and insulation resistance of the safety input cabling from the safety sensor or switch to the drive's X150 terminals.
3. Test the external safety sensor or switch used for SLS by manually actuating it and observing signal changes at the drive's inputs.
4. Inspect the drive's safety module diagnostic LEDs (if available) for specific indications of input channel failures or inconsistencies.
5. Perform a safety test of the SLS function as per the drive's safety manual to identify the exact point of inconsistency in the safety chain.