Siemens · SINAMICS G120
The drive is unable to switch on and remains in the READY state because its start is inhibited. This can be caused by a deactivated gate driver, an active safety function such as Safe Torque Off (STO), Safe Stop 1 (SS1), or Safe Limited Speed (SLS), or another inhibit condition, preventing motor operation.
Click steps to track your progress.
1. Verify the status of the Safe Torque Off (STO) input signals (e.g., F-DI0, F-DI1 at X150) and ensure they are active (e.g., 24VDC) to enable STO release.
2. Check the status of all active safety functions (e.g., r0947, r0948) and ensure no safety function is requesting an inhibited state.
3. Confirm that the main enable command (e.g., associated with P0840) is received and active from the control system (e.g., PLC or HMI).
4. Inspect the status of general digital inputs (e.g., DI0, DI1 at X101) to ensure the drive receives the necessary run commands.
5. Power cycle the drive by disconnecting and reconnecting the main supply voltage, then re-evaluate the drive's readiness for operation.