Siemens · SINAMICS G120
The dynamisation timer (r9660) for safety functions has expired, requiring a new dynamisation test. This test verifies the integrity of the safety circuit, and without performing it, the safety functions may not be fully trusted, preventing safe operation and potentially leaving the machine in an unsafe state.
Click steps to track your progress.
1. Initiate the dynamisation test by cycling the associated safety input signals (e.g., F-DI0, F-DI1) as required by the safety circuit design.
2. Verify parameter P9660 (Dynamisation time) to ensure the interval is appropriate for the application and the required safety integrity level.
3. If safety functions are controlled by an external safety PLC, check its program to ensure it is correctly managing the dynamisation cycles.
4. Review the drive's safety manual for specific instructions on performing the dynamisation test for the implemented safety functions.
5. Check the status of the safety inputs (e.g., F-DI0, F-DI1 at X150) to confirm they are physically changing state during the test procedure.