Siemens · SINAMICS G120
The system is actively waiting for communication, likely with the F host. This alarm indicates a potential disruption or delay in the communication link, preventing the inverter from receiving necessary commands or operational data from the host controller.
Click steps to track your progress.
1. Verify the physical connection of the communication cable (e.g., Ethernet, PROFIBUS) between the drive and the F host, checking for secure connectors.
2. Confirm that the F host (e.g., PLC) is powered on, in run mode, and configured to communicate with the drive (e.g., check network diagnostics on PLC).
3. Check the network configuration parameters in the drive (e.g., p88xx for PROFINET, p918 for PROFIBUS address) and ensure they match the host controller's settings.
4. Use network diagnostic tools (e.g., ping test, bus analyzer) to check for communication integrity and identify packet loss or errors.
5. Cycle power to both the drive and the F host to re-initialize communication interfaces.