Siemens · SINAMICS G120
The Safely Limited Speed (SLS) has been exceeded, meaning the motor is moving faster than the configured safe speed limit. This indicates a failure in speed monitoring or an incorrect speed setpoint from the higher-level control, posing a significant safety risk.
Click steps to track your progress.
Compare the actual motor speed (r0021) with the Safely Limited Speed threshold (P30630) using the drive's diagnostic display.
Verify the encoder feedback signal integrity (e.g., A/B/Z channels) using an oscilloscope at the drive's encoder input terminals (e.g., X45) to check for noise or loss.
Review and adjust the Safely Limited Speed threshold (P30630) and associated ramp parameters (P30631, P30632) to match machine requirements.
Check for external forces or loads (e.g., gravity, kinetic energy from coupled machinery) that could be driving the motor beyond the set limit.
Initiate a speed sensor calibration or offset adjustment (e.g., P0400) if encoder scaling or zero-speed detection is inaccurate.