F00072

USS Setpoint Fault

Siemens · SINAMICS G120

What does F00072 mean?

The drive has failed to receive setpoint values via the USS (Universal Serial Interface) communication protocol within the configured telegram off time. This suggests a problem with the USS master device or the communication settings, causing the drive to lose its operational commands and halt controlled operation.

Common Causes

  • RS485 communication wiring error (e.g., A/B lines swapped, common ground missing, loose terminals X300) between the master device and the drive.
  • Incorrect USS communication parameters (e.g., P2010 Baud rate, P2011 Address, P2013 Telegram off time) on either the USS master or the drive.
  • The USS master device (e.g., PLC or HMI) is not sending telegrams or is experiencing an internal fault.
  • Excessive electromagnetic interference (EMI) on the RS485 bus due to unshielded cables or improper grounding, leading to data corruption.
  • Missing or incorrectly placed terminating resistors (e.g., P2015 bit 0 for internal termination) on the USS bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Inspect RS485 wiring on terminals X300 (A/B/common) for correct polarity, secure connections, and shield grounding.

  2. 2

    2. Confirm that drive parameters P2010 (Baud rate), P2011 (USS address), and P2013 (Telegram off time) precisely match the USS master settings.

  3. 3

    3. Use a multimeter to check for correct RS485 bus voltage levels (differential signal) at the drive terminals when the master is transmitting.

  4. 4

    4. Increase the drive's P2013 (USS telegram off time) to 250ms to account for potential communication delays and retest.

  5. 5

    5. Verify that RS485 bus termination (P2015 bit 0 for internal termination) is correctly configured, typically active at both physical ends of the bus.