Siemens · SINAMICS G120
A watchdog timer reset has occurred, indicating a critical software error within the drive's control unit. This signifies that the software has become unresponsive or entered an unexpected state, leading to a system reset and potential loss of control over the connected motor.
Click steps to track your progress.
1. Perform a power cycle of the drive and observe if the fault persists, as this can sometimes clear transient software states.
2. Back up existing drive parameters, then perform a factory reset (P0010=30, P0970=1) and reconfigure essential parameters.
3. Check the drive's DC link voltage (r0026) for stability and ensure the input power supply is within specified limits.
4. Update the drive's firmware to the latest stable version using STARTER or TIA Portal to address potential software bugs.
5. Inspect the control unit (e.g., CU320-2) for any visible damage, loose internal connections, or signs of overheating.
6. Temporarily reduce the complexity of background tasks or communication load (if applicable) and monitor for recurrence of the fault.