Siemens · SINAMICS G120
This fault indicates a timeout during a safety reset operation on either the P1 or P2 processor, meaning the system failed to reset within the expected timeframe. This can prevent the drive from reinitializing correctly, often caused by an unexpected system hang during the reset process.
Click steps to track your progress.
1. Cycle main power to the drive (full power-off/power-on cycle) and observe if the fault clears upon restart.
2. Check for any available firmware updates for the drive's safety module and perform an update if necessary, ensuring full parameter backup first.
3. Monitor internal diagnostic LEDs on the safety module (if present) for specific boot sequence or error indications.
4. Verify the 24VDC control supply voltage at designated terminals (e.g., X9/X10) remains stable during power-up and reset attempts.
5. Access drive diagnostics via the HMI or engineering tool to check status registers related to safety processor boot (e.g., r9790, r9791).